Low pressure heat shrinkable busbar ( 1kv continuous busbar protects heat shrinkable sleeve WMPG-1K )
The low-pressure heat-shrinkable busbar is made of environmentally friendly polyolefin heat-shrinkable materials bombarded and crosslinked with high-energy electron beams. It limits PBB, PBBD, PBBE and heavy metals and other harmful substances to the environment. It does not produce toxic gases and harmful substances during combustion. High insulation strength and resistance to electric carbon traces, suitable for anti-corrosion and insulation protection of busbars and electrical equipment.
Features
● Shrinkage ratio: 2: 1 (1kV, 35kV), 2.5: 1 (10kV busbar)
● Shrinkage temperature: 84 ℃ ~ 125 ℃
● Working temperature: -40 ℃ ~ 125 ℃
● Environmental protection, high strength, good elasticity, flame retardant, soft
Product Usage
● Functional uses: electrical insulation, mechanical protection, reducing phase spacing, making joint boxes.
● Application field: Power industry
Executive Standard
a.GB/T 1059-2007
b. Environmental certification: RoHS,
c. Color standard: iron red, yellow, green, black
1kv continuous busbar protection heat shrinkable sleeve WMPG-1K physical and chemical electrical performance table
|
performance
|
unit
|
Performance
|
Test method / condition
|
|
Tensile Strength
|
MPa
|
≥10.4 (before aging)
|
GB/T 1040
130 ℃ × 168h
|
|
|
|
≥7.3 (after aging)
|
|
|
Elongation at break
|
%
|
≥300 (before aging)
|
GB/T 1040,GB/T7141
130 ℃ × 168h
|
|
|
|
≥100 (after aging)
|
|
|
Thermal shock
|
-
|
No stickiness, no cracking
|
JB 7829 Appendix D. (160 ℃ × 4h)
|
|
Cold bending resistance
|
-
|
Does not crack
|
-30 ℃ × 4h
|
|
Breakdown strength
|
kv/mm
|
≥25
|
GB/T 1408.1
|
|
Volume resistivity
|
Ω.cm
|
≥1 × 1014
|
GB/T 1410
|
|
Radial shrinkage
|
%
|
≥50
|
|
|
Partial wall rate **
|
%
|
≤30
|
UL 224
|
|
Flame retardant
|
-
|
≥30
|
GD / T 2406
|
|
Water absorption
|
%
|
≤0.5
|
ISO 62-1980
|
|
Power frequency withstand voltage *
|
kv/mm
|
≥30kV.1min
|
GB/T 1408.1
|
|
Shore Hardness (Shore A)
|
|
≤90
|
GB 2401
|
* This indicator applies to 10KV busbars. When conducting this index test, the product must be uniformly shrunk on the busbar, and the thickness of the thinnest part should be greater than 2mm, and the length of the busbar should be ≥1200mm.
** 35kV continuous busbar deviation rate≤50%
1kv continuous busbar protection heat shrinkable sleeve specifications table
|
specification
|
Applicable busbar width
|
Size before shrinking (mm)
|
Dimensions after shrinking (mm)
|
standard packaging
|
|
|
|
the inside diameter of
|
Wall thickness
|
the inside diameter of
|
Wall thickness
|
M / dish
|
|
1kV WMPG 30
|
30
|
31.5 ± 1.0
|
0.5 ± 0.15
|
≤15.0
|
1.00 ± 0.15
|
50
|
|
1kV WMPG 35
|
35
|
36.5 ± 1.0
|
0.5 ± 0.15
|
≤17.5
|
1.00 ± 0.15
|
50
|
|
1kV WMPG 40
|
40
|
41.5 ± 1.0
|
0.55 ± 0.15
|
≤20.0
|
1.00 ± 0.15
|
50
|
|
1kV WMPG 45
|
45
|
46.5 ± 1.0
|
0.55 ± 0.15
|
≤22.5
|
1.00 ± 0.15
|
25
|
|
1kV WMPG 50
|
50
|
≥50
|
0.55 ± 0.15
|
≤25.0
|
1.10 ± 0.15
|
25
|
|
1kV WMPG 60
|
60
|
≥60
|
0.60 ± 0.15
|
≤30.0
|
1.20 ± 0.15
|
25
|
|
1kV WMPG 70
|
70
|
≥70
|
0.65 ± 0.15
|
≤35.0
|
1.30 ± 0.20
|
25
|
|
1kV WMPG 75*
|
75
|
≥75
|
0.65 ± 0.15
|
≤38.0
|
1.30 ± 0.20
|
25
|
|
1kV WMPG 80
|
80/100
|
≥80
|
0.65 ± 0.15
|
≤40.0
|
1.30 ± 0.20
|
25
|
|
1kV WMPG 85*
|
80/100
|
≥85
|
0.65 ± 0.15
|
≤43.0
|
1.30 ± 0.20
|
25
|
|
1kV WMPG 90
|
100
|
≥90
|
0.65 ± 0.15
|
≤45.0
|
1.30 ± 0.20
|
25
|
|
1kV WMPG 100
|
100/120
|
≥100
|
0.65 ± 0.20
|
≤50.0
|
1.30 ± 0.20
|
25
|
|
1kV WMPG 120
|
150
|
≥120
|
0.65 ± 0.20
|
≤60.0
|
1.30 ± 0.20
|
25
|
|
1kV WMPG 150
|
180
|
≥150
|
0.65 ± 0.20
|
≤70.0
|
1.30 ± 0.20
|
25
|
|
1kV WMPG 180
|
MAX
|
≥180
|
0.65 ± 0.30
|
≤90.0
|
1.30 ± 0.30
|
25
|
|
1kV WMPG 210*
|
MAX
|
≥210
|
0.65 ± 0.30
|
≤105.0
|
1.30 ± 0.30
|
25
|
|
1kV WMPG 230*
|
MAX
|
≥230
|
0.65 ± 0.30
|
≤115.0
|
1.30 ± 0.30
|
25
|
|
1kV WMPG 250*
|
MAX
|
≥250
|
0.65 ± 0.30
|
≤125.0
|
1.30 ± 0.30
|
25
|
|
Note: The specifications with * indicate that no inventory is required, and special orders need to be ordered
|
|
|
|